Technical Tips

 

Question:

How do I use the PLC Signal Strength Test Set?

Answer:

The PLC test set is a very handy and easy to use device for troubleshooting communications problems. However, it must be used properly to gather valid signal strength information. The good news is that the test procedure is really very simple when it is done systematically. Follow these simple steps to get valid signal strength information:

 

·        Place the greenhouse’s critical systems under manual control so that the GEM3 system can be shut down safely for ten minutes or more.

·        Shut down the GEM3 program by typing <Alt>, then <Q> to quit DESQview, then <Y> for yes. This will cause the program to stop polling sensors and devices in the greenhouse.

·        Go to the Translator Unit and turn its power OFF. Now find the S4 strap that is located in the upper left-hand corner of the circuit board. Install a special shorting strap over the left-hand 3 pins of S4. (See Figure 1 at the end of this document) A shorting strap fixture is available from Q-Com (one should be sent with the tester). When you turn the power on again the Translator should begin to transmit a continuous signal on the powerline throughout the GEM3 system for testing purposes.

·        Go to all of your sensor units throughout the greenhouse and measure the strength of the signal arriving from the Translator by plugging in the test set near the sensor (see note below) and turning the knob to higher and higher levels until the light goes out. Turn the knob back one setting and verify that the light comes on and then record this signal level and location (a sample chart is included at the end of this document). Do this at all sensors where communications have been suspect.

i    Please Note: For this signal reading to be valid, you MUST have your tester attached to the same phase as the sensor unit you are testing.

·        Now go back to the Translator and remove the strapping fixture (remember to turn off the power while working inside the box). When you turn the power back ON, the translator should no longer send a continuous PLC signal, but return to normal operating mode.

·        Go to any suspect sensor unit, turn off the power, and strap out the top 3 pins of JP1 (located on the left edge of the motherboard, just below the little green light). When the power is restored, this will cause this particular sensor to transmit its full strength signal continuously back to the translator unit. (See Figure 2) Go to an outlet in the area of the translator that you are sure is connected to one of the phases coupled to the translator unit (see note below) and plug in the test set. Repeat the process described in step #3 to record the signal level for this sensor. Remove the strap and then repeat this test for any or all sensors in the system that you feel may be experiencing communication difficulties.

i    Please Note: The signal arriving back at the translator from the sensor unit is arriving on one particular phase.  In a multi-phase system (like 220 single-phase - this name is misleading, there are actually 2 phases to neutral, or 208 3-phase) the sensor signal will come back very weak on the phases that are not powering the sensor unit.  Therefore, you should connect your test set to all available phases and use the highest reading on your test chart.

·        Remove all strapping fixtures from any sensor or translator in the system. This will make the system ‘quiet’ as long as the GEM3 program is still shut down. Now you can go to any part of the system where you were experiencing problems and record ‘noise’ levels. Do this the same way you did for signal testing; by turning the knob down (usually to very low settings) until the light on the tester illuminates and then up again until it extinguishes. Go back down one notch and verify that the light comes on again, then record this level as ‘Noise’ on your list for this location.

·        Restart the GEM3 program as soon as you are finished with the testing and return all controls to automatic operation.

·        Send your list of recorded signal and noise measurements, listed by location, to Q-Com for analysis. A sketch of the layout and the locations of the translator and sensor units would also be helpful in resolving the problem.

 

With this information, we should be able to help you find the source of your problem very quickly.

Sample Test Chart

 

Note: In this test procedure, the sensor is the important element, whether in the translator-testing phase, or the sensor-testing phase. In the translator-testing phase, you will be located at or near a particular sensor, and that location should be recorded in first column. In the sensor-test phase, a particular sensor will be transmitting and you will be testing at the translator for signal strength. So again, the sensor location is the key. That is why there is a column for each testing phase beside each sensor location listed in column 1 of the chart.

 

In the noise testing phase there is a special line just for the translator, so you can record the noise level in its area with the GEM3 system shut down.

 

Sensor Location Tested

Translator Test
Signal Level Recorded @ Sensor

Sensor Test Phase
Signal Level Recorded @ Translator

Noise Test Phase
Signal Level Recorded

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Translator

---------N/A----------

------------N/A-----------

 

 

If you need further help or information, give our Customer Service Department a call at (949) 833-1000 or (904) 963-5851.  Or, visit our web site @ www.qcomcorp.com for further technical support.